DIESEL GENERATOR SET POWERED BY PERKINS 400/230 VOLT- 50 HZ.,1500 RPM.
Gen Set Model |
Perkins Type |
Standby Rating |
Prime Rating |
||
KVA. |
KW. |
KVA. |
KW. |
||
TP10T |
403D – 11G |
10 |
8 |
9 |
7 |
TP15T |
403D – 15G |
15 |
12 |
13 |
10 |
TP22T |
404D - 22G |
22 |
18 |
20 |
16 |
TP33T |
1103A - 33G |
33 |
26 |
30 |
24 |
TP50T |
1103A - 33TG1 |
50 |
40 |
45 |
36 |
TP66T |
1103A - 33TG2 |
66 |
53 |
60 |
48 |
TP88T |
1104A - 44TAG1 |
88 |
70 |
80 |
64 |
TP110T |
1104C – 44TAG2 |
110 |
88 |
100 |
80 |
TP115T |
1006TG2A |
110 |
88 |
100 |
80 |
TP150T |
1006TAG |
150 |
120 |
135 |
108 |
TP155T |
1106A – 70TAG1 |
150 |
120 |
135 |
108 |
TP165T |
1006TAG2 |
165 |
132 |
150 |
120 |
TP170T |
1106A - 70TAG2 |
165 |
132 |
150 |
120 |
TP200T |
1106A – 70TAG3 |
200 |
160 |
180 |
144 |
TP220T |
1106A – 70TAG4 |
220 |
176 |
200 |
160 |
TP250T |
1306C - E87TAG4 |
250 |
200 |
227 |
184 |
TP275T |
1306C - E87TAG6 |
275 |
220 |
250 |
200 |
TP300T |
1606A – E93TAG4 |
300 |
240 |
275 |
220 |
TP330T |
1606A – E93TAG5 |
330 |
264 |
300 |
240 |
TP385T |
2206A – E13TAG2 |
385 |
308 |
350 |
280 |
TP440T |
2206A – E13TAG3 |
440 |
3520 |
400 |
320 |
TP500T |
2506A – E15TAG1 |
500 |
400 |
454 |
360 |
TP550T |
2506A – E15TAG2 |
550 |
440 |
500 |
400 |
TP660T |
2806A – E18TAG1A |
660 |
528 |
600 |
480 |
TP700T |
2806A – E18TAG2 |
700 |
560 |
650 |
520 |
TP825T |
4006 – 23TAG2A |
825 |
660 |
750 |
600 |
TP880T |
4006 – 23TAG3A |
880 |
704 |
800 |
640 |
TP1100T |
4008TAG2A |
1100 |
880 |
1000 |
800 |
TP1375T |
4012 – 46TWG2A |
1375 |
1100 |
1250 |
1000 |
TP1650T |
4012 – 46TAG2A |
1656 |
1325 |
1505 |
1204 |
TP1875T |
4012 – 46TAG3A |
1875 |
1500 |
1705 |
1364 |
TP2000T |
4016TAG1A |
2028 |
1622 |
1844 |
1476 |
TP2250T |
4016TAG2A |
2250 |
1800 |
2058 |
1646 |
TP2500T |
4016 – 61TRG3 |
2420 |
1936 |
2200 |
1760 |
RATING : All rating data based on operation under
ISO 3046 ,BS5514 , DIN6271 , ISO8528
STANDBY POWER : Standby ratings are for the supply of
emergency power at variable load in the event of a main
power network failure up to a maximum of 500 hours per
year , No overload in permitted.
PRIME POWER : Prime ratings are suitable for continuous
electrical power (at variable load in lieu of main power
network). There is no limitation to the annual hours of
operation and all models can supply 10 % overload power
for 1 hour in 12 hours.