DIESEL GENERATOR SET POWERED BY CUMMINS 400/230 VOLT- 50 HZ.,1500 RPM.

 
Gen Set Model

Cummins Type

Standby Rating

Prime Rating

KVA.

KW.

KVA.

KW.

TC30T

4B3.9 – G2

30

24

27

22

TC44T

4BT3.9 – G2

44

35

40

32

TC62T

4BTA3.9 – G2

62

50

56

45

TC70T

4BTA3.9 – G2

70

56

65

52

TC90T

4BTA3.9 – G11

90

72

80

64

TC100T

6BT5.9 – G2

103

82

94

75

TC115T

6BT5.9 – G2

115

92

105

84

TC125T

6BTA5.9 – G2

125

100

115

92

TC145T

6BTAA5.9 – G2

145

116

135

108

TC165T

6BTAA5.9 – G12

165

132

150

120

TC175T

6CTA8.3 – G2

175

140

160

128

TC200T

6CTA8.3 – G2

200

160

180

145

TC220T

6CTAA8.3 – G2

215

172

200

160

TC265T

6LTAA8.9 – G2

264

211

250

200

TC275T

6LTAA8.9 – G3

275

220

250

200

TC315T

NTA855 – G1A

313

250

275

220

TC350T

NTA855 – G1B

340

272

310

248

TC375T

NTA855 – G2A

375

300

344

275

TC385T

NTA855 – G4

388

310

350

280

TC410T

NTAA855 – G7

413

330

375

300

TC450T

NTAA855 – G7A

450

360

 N/A N/A 
TC500T

KTA19 – G3

500

400

450

360

TC550T

KTA19 – G3A

563

450

500

400

TC550T

KTA19 – G4

563

450

500

400

TC550T

KTAA19 – G5

590

472

525

420

TC625T

KTAA19 – G5

631

505

525

420

TC690T

KTAA19 – G6A

688

550

N/A

N/A

TC715T

QSK19 – G4

713

570

650

520

TC750T

QSK19 – G11

738

590

670

536

TC800T

KT38 – GA

800

640

725

580

TC825T

KTA38 – G2

825

660

750

600

TC880T

KTA38 – G2B

888

710

800

640

TC1000T

KTA38 – G2A

1000

800

910

728

TC1100T

KTA38 – G5

1100

880

1000

800

TC1250T

KTA38 – G9

1230

984

N/A

N/A

TC1375T

KTA50 – G3

1345

1076

1250

1000

TC1650T

KTA50 – G8

1650

1320

1375

1100

TC1650T

KTA50 – GS8

1650

1320

1500

1200

RATING

STANDBY POWER (ESP) : The standby power rating is 
applicable for supplying emergency power for the duration of
a utility power interruption. No overload, utility parallel or 
negotiated outage operation capability is available at this 
rating.

PRIME POWER (PRP) : Prime power is available for an 
unlimited number of annual hours in variable load application, in
accordance with GB/T2820-97(eqvISO8528); A 10% overload 
capability is available for a period of 1 hour within a 12-hour 
period of operation.